During PVB Air Inlet Test, Air inlet valve does not open, as field test kit drops to 0.0 psid. What does this indicate? {Ans: 1. Air inlet disc stuck to seat 2. Broken or missing air inlet spring 3."O|d style" pressure vacuum breaker (non- loaded air inlet valve) 4. It is an SVB (See Book 9.5)}What is the purpose and requirement of the SVB ) Spil-Resistant Pressure Vacuum Breaker Assembly) Test # 1: Tightness of Check Valve (USC 10th ed pg 308)? {Ans: Purpose: To determine the static differential pressure across the check valve. Requirement: The static differential pressure across the check valve shall be at least 1.0 psid.}During SVB (Air Inlet Opening Point) Test 2, water runs continuously from vent screw valve. What does this indicate? {Ans: 1. Leaking No. 1 shutoff valve}When testing the RP backflow device, and while observing the gauge, and introducin HP water behind the #2CV (RP Test Procedure 2, Step 3), and the RV begins to discharge, what action(s) do you take to troubleshoot the equipment? {Ans: 1. You have a leaking # 2 Check Valve 2. Proceed by reestablishing and give the #2CV a second chance, if discharge continues