NABCEP PV ASSOCIATE RETAKE EXAM|RETAKE PRACTICE EXAM LATEST EXAM 2024|ALL QUESTIONS AND CORRECT VERIFIED ANSWERS|100% GUARANTEED TO PASS!|ALREADY GRADED A+/BRAND NEW VERSION An off-grid installation has a 1HP pump that is on 10% of the time and a 20W light that is on 100% of the time. What is the monthly energy use? - ANSWER-68KWh 1HP = 746W 746W * 0.1 * 24hours * 30days = 53712Wh 20W * 24hrs * 30days = 14400Wh 14400 + 53712 = 68112Wh 68kWh What kind of ground faults do most inverters detect? - ANSWER-DC Inverters detect dc ground faults. AC ground faults are detected on the AC side of the inverter at the distribution paned (MSP, load center). Most inverters are not connected to high or medium voltage. Medium voltage is thousands of volts, large utility scale inverters are connected to medium voltage via a transformer Current carrying ability of a conductor (wire) is called - ANSWER-Ampacity According to ohms law and voltage drop, the relationship between voltage drop and current is - ANSWER-Proportional. Ohms law: V = I*R More current makes more voltage drop. This is a reason why we need a larger wire with more current, so the wire resistance is